P2 專題選修 Specialist Elective · 8 分鐘 / min

製冷循環的四個環節 The Four Stages of Refrigeration

用蒸發、壓縮、冷凝和節流串起熱的搬運路徑。

開啟定量聯算教學 Open the Quantitative Engineering Lab

互動工程卡 Interactive Engineering Card

沿四個元件定位熱量與壓縮機功。 Trace heat and compressor work through four components.

壓縮機 / Compressor 冷凝器 / Condenser 節流裝置 / Expansion device 蒸發器 / Evaporator
簡化單段蒸氣壓縮循環。 Simplified single-stage vapour-compression cycle.
Qcond = Qevap + Wcomp
Qₑ
蒸發器吸熱 Evaporator heat absorbed kW
W
壓縮機輸入功 Compressor work input kW

穩態,忽略其他熱損失。壓縮機功指傳給冷媒的功。 Steady state with other heat losses omitted. Compressor work is the power transferred to the refrigerant.

易錯做法 Common Mistake

將冷凝器排熱當成蒸發器冷量。 Equate condenser heat rejection with evaporator cooling.

工程核對 Engineering Check

追蹤冷媒取得的兩項能量,兩者皆經冷凝器排放。 Add the heat absorbed and the work transferred to the refrigerant; both leave via the condenser.

延伸至相關知識卡 Continue to Related Cards · 離心式冷水機與喘振 Centrifugal Chillers and Surge · 冷卻塔的濕球、溫降與逼近度 Cooling Towers: Wet Bulb, Range and Approach

中英術語 Key Terms
製冷循環
refrigeration cycle
壓縮機
compressor
冷凝器
condenser
膨脹裝置
expansion device
蒸發器
evaporator

查術語定義與用法 Look Up Definitions and Usage

學習目標 Learning Objective

用箭頭說明冷媒走一圈時,哪裡吸熱、哪裡耗功、哪裡排熱。

Identify heat absorption, input work and heat rejection.

核心概念 Key Concepts

蒸發器讓冷媒吸收冷凍水或空氣的熱。壓縮機提高冷媒壓力。冷凝器把熱送給冷卻介質。節流裝置降壓,讓冷媒回到能吸熱的狀態。過熱與過冷都是溫度相對對應壓力的飽和溫度的差。

The evaporator accepts heat from water or air. The compressor raises refrigerant pressure. The condenser rejects heat. Expansion lowers pressure so the refrigerant can absorb heat again. Superheat or subcooling is relative to saturation temperature at the relevant pressure.

公式與單位 Formulas and Units

  • 穩態簡化熱平衡為 Q̇冷凝 ≈ Q̇蒸發 + P壓縮,統一用 kW,並忽略殼體等外部散熱。
  • 過熱度或過冷度以 K 表示,查飽和溫度須使用該冷媒及合適的壓力資料。

At steady state and ignoring case losses, condenser heat rejection ≈ evaporator load + compressor input, all in kW. Superheat and subcooling are temperature differences in K. Use refrigerant-specific data.

常見錯誤 Common Mistakes

  • 把冷量當壓縮機功率。把吸熱、排熱與輸入功分別畫出。
  • 用錯壓力側的飽和溫度。把狀態點和壓力分組。

Do not confuse cooling capacity with compressor power or use the wrong saturation pressure.

例題 Worked Example

呼出計算器 Open Calculator

蒸發器吸熱 38 kW,壓縮輸入 9 kW。穩態排熱?

製冷循環的四個環節 / The Four Stages of Refrigeration 2341 1 → 2 → 3 → 4 → 1 38 kW + 9 kW = 47 kW

1 蒸發器,2 壓縮機,3 冷凝器,4 膨脹閥。 1 Evaporator, 2 compressor, 3 condenser, 4 expansion valve.

  1. 蒸發器吸熱 38 kW Evaporator takes 38 kW
  2. 壓縮機輸入 9 kW Compressor input 9 kW
  3. 冷凝器排熱 47 kW Condenser rejects 47 kW
例題圖解 · 教學工況 Worked Diagram · Teaching Conditions
展開解題步驟 Show Solution

忽略其他散熱,冷凝器排熱約 38 + 9 = 47 kW。

完整示範與練習銜接 Worked Method and Practice Bridge

按蒸發器 → 壓縮機 → 冷凝器 → 膨脹閥 → 蒸發器閉合箭頭;把前兩股能量畫入,排熱畫出。忽略外殼散熱,47 應大於 38。 Close the loop through evaporator → compressor → condenser → expansion valve → evaporator. Draw heat and work entering and condenser heat leaving. Neglecting casing losses, 47 should exceed 38.

1 個小練習 Practice Problem

呼出計算器 Open Calculator

一個虛構循環從冷水吸收 54 kW,壓縮輸入 11 kW。畫四段循環和三支能量箭頭,估算冷凝器排熱。

作答後核對答案 Check Answer

由蒸發器 → 壓縮機 → 冷凝器 → 膨脹裝置 → 蒸發器。外部箭頭是蒸發吸熱 54 kW、壓縮輸入 11 kW、冷凝排熱 65 kW。

延伸思考與參考 Further Study and References

1 個蘇格拉底式問題 Socratic Question

如果冷凝器排熱量比蒸發器吸熱量大,你會用哪一段能量流解釋差值?

Which energy input accounts for the condenser heat being higher than evaporator heat?

公開參考連結佔位符 Public Reference Placeholder

〔待導師填入:公開的蒸氣壓縮製冷循環與冷媒狀態教學〕