P2 專題選修 Specialist Elective · 8 分鐘 / min

離心式冷水機與喘振 Centrifugal Chillers and Surge

認識葉輪、擴壓、壓力提升及部分負荷限制。

開啟定量聯算教學 Open the Quantitative Engineering Lab

互動工程卡 Interactive Engineering Card

從壓縮機剖面辨識葉輪與擴壓段,以絕壓比和運行資料判斷下一項檢查。 Identify the impeller and diffuser, then use absolute pressure ratio and operating evidence to choose the next check.

入口 / Suction 擴壓段 / Diffuser 葉輪 / Impeller 250 kPa abs 750 kPa abs
離心壓縮機教學工況|儀表均顯示絕壓。 Centrifugal compressor teaching case | Both instruments display absolute pressure.
PR = P₂,abs / P₁,abs
Pabs = Pgauge + Patm
P₁
入口絕壓 Suction absolute pressure kPa abs
P₂
出口絕壓 Discharge absolute pressure kPa abs

剖面為原理示意。壓力比是無因次比值。工況能否運行須用原廠圖及量測判定,本卡不預測喘振邊界。 This is a schematic section. Pressure ratio is dimensionless. Operating limits require the manufacturer’s map and measurements. The card does not predict a surge line.

易錯做法 Common Mistake

把表壓直接相除,或只憑壓力比判定喘振。 Divide gauge pressures directly or diagnose surge from pressure ratio alone.

工程核對 Engineering Check

先轉絕壓。再對照原廠圖、流量、轉速與壓力趨勢。 Convert to absolute pressures first. Then check the map, flow, speed and pressure trend.

羅徹斯特大學區域供冷機房。照片作場景參考,來源未指明圖中各台的壓縮機型式。 / University of Rochester district cooling plant. The photograph shows the setting. Its source does not identify the compressor type of each unit.
羅徹斯特大學區域供冷機房。照片作場景參考,來源未指明圖中各台的壓縮機型式。 University of Rochester district cooling plant. The photograph shows the setting. Its source does not identify the compressor type of each unit. Z22 · Wikimedia Commons · CC BY-SA 4.0 · 960 px 縮圖 960 px thumbnail

Trane · Chilled-Water Systems

延伸至相關知識卡 Continue to Related Cards · 製冷循環的四個環節 The Four Stages of Refrigeration · COP、kW/冷凍噸與部分負荷 COP, kW per Ton and Part Load

中英術語 Key Terms
離心式冷水機
centrifugal chiller
喘振
surge
壓力比
pressure ratio
壓縮機圖
compressor map
提升幅度
lift

查術語定義與用法 Look Up Definitions and Usage

學習目標 Learning Objective

解釋離心式冷水機如何提升冷媒壓力,並辨認為何有些工況不穩定。

Explain pressure rise and why some operating points are unstable.

核心概念 Key Concepts

葉輪向冷媒加速,擴壓段將部分速度能轉為壓力。容量可由轉速及入口導葉等調節,實際做法視設備而定。流量太低而壓力提升要求較高時,某些工況可能接近喘振邊界,出現不穩定流動。潤滑或磁浮軸承是機組設計差異。

An impeller accelerates refrigerant, and a diffuser converts part of its velocity to pressure. Speed or inlet guide vanes may control capacity. Low flow with high required pressure rise may approach surge. Bearings and lubrication vary by design.

公式與單位 Formulas and Units

  • 壓力比 = 出口絕對壓力 ÷ 入口絕對壓力。絕壓使用同一單位後比值無單位。
  • 若機組資料以飽和溫度表示提升幅度(lift),可用冷凝飽和溫度減蒸發飽和溫度,單位 K。先核對型錄使用的定義。
  • 壓縮機圖上的流量、壓力比和速度線要按型錄的基準及單位查閱。

Pressure ratio = outlet absolute pressure / inlet absolute pressure. Some catalogs use condensing minus evaporating saturation temperature for lift in K. Use the map conventions and speed line.

常見錯誤 Common Mistakes

  • 用表壓直接求壓力比。先核對基準。
  • 把低負荷當作所有機組都安全節能。先查原廠運行包絡和量測條件。

Use absolute pressures. Consult the operating envelope before assuming low load is stable or efficient.

例題 Worked Example

呼出計算器 Open Calculator

壓縮機入口 250 kPa 絕壓、出口 750 kPa 絕壓。壓力比?

離心式冷水機與喘振 / Centrifugal Chillers and Surge 3BA p₂/p₁V̇
  1. 入口 250 kPa 絕壓 Inlet 250 kPa absolute
  2. 出口 750 kPa 絕壓 Outlet 750 kPa absolute
  3. 壓比 3,等壓比線 Ratio 3, constant-ratio line
例題圖解 · 教學工況 Worked Diagram · Teaching Conditions
展開解題步驟 Show Solution

750 ÷ 250 = 3.0,無單位。運行點仍需要流量與速度才能放到設備圖上。

完整示範與練習銜接 Worked Method and Practice Bridge

橫軸為流量、縱軸為壓比。同為壓比 3 時,較低流量點在同一水平線左側。是否接近喘振仍需該轉速下的設備圖。 Put flow on x and pressure ratio on y. At ratio 3, the lower-flow point is farther left on the same horizontal line. Surge proximity needs the machine map at its actual speed.

1 個小練習 Practice Problem

呼出計算器 Open Calculator

用紙畫「流量—壓力比」方格。樣本 A 與 B 的壓力比相同,B 的流量更低,標出 B 相對 A 的位置,再列一項判定是否接近限制時需要的資料。

作答後核對答案 Check Answer

以流量為橫軸時,B 在 A 左側且同高。需取得該工況和轉速的壓縮機圖及喘振界線。

延伸思考與參考 Further Study and References

1 個蘇格拉底式問題 Socratic Question

如果一台機組開始出現流量不穩,你會請專業人員提供哪一張運行圖,而不是只聽聲音判斷?

What map would you ask a specialist for when flow is unstable?

公開參考連結佔位符 Public Reference Placeholder

〔待導師填入:公開的離心式冷水機及壓縮機運行圖入門〕