P2 專題選修 Specialist Elective · 9 分鐘 / min

COP、kW/冷凍噸與部分負荷 COP, kW per Ton and Part Load

在相同邊界與工況下比較冷量、功率和部分負荷表現。

互動工程卡 Interactive Engineering Card

按同一量測邊界核算 COP。 Calculate COP for a consistent measurement boundary.

  1. 熱量表 Heat meter
  2. 冷水機 Chiller
  3. 電表 Power meter
同時讀取冷水機冷量與輸入功率。 Read chiller cooling and electrical power at the same time.
COP = Qcool/Pelectric
Qcool
冷量 Cooling output kW
P
輸入電功率 Electrical input kW

示例限冷水機,表計不含塔和泵。 Chiller-only example. The meter excludes towers and pumps.

易錯做法 Common Mistake

拿額定冷量和不同時點的電表值相除。 Use rated capacity with a meter value from a different time.

工程核對 Engineering Check

先對齊量測時間與設備邊界,再將輸出除以輸入。 Align timing and equipment boundary, then divide output by input.

延伸至相關知識卡 Continue to Related Cards · 冷水機簡化能耗模型 A Simple Chiller Energy Model · 全站節能與供水重設取捨 Plant Efficiency and Supply Temperature Reset

中英術語 Key Terms
性能係數
coefficient of performance (COP)
部分負荷比
part-load ratio (PLR)
冷凍噸
ton of refrigeration (TR)

查術語定義與用法 Look Up Definitions and Usage

學習目標 Learning Objective

計算冷水機 COP 與 kW/TR,解讀部分負荷資料時標明工況。

Compute efficiency and state the part-load operating conditions.

核心概念 Key Concepts

一台機組在不同冷凍水溫度、冷卻水溫度與負荷下,電功率可能不同。部分負荷性能須在適用範圍內讀取。整合部分負荷指標來自約定的多個測試點,用來比較,實際建築的年用電仍由自己的運行情境決定。

A chiller's power depends on load and both water temperatures. Read part-load data within their range. An integrated rating compares specified test points. Annual energy depends on actual operations.

公式與單位 Formulas and Units

  • COP = 冷量 kW ÷ 用電功率 kW。以 1 TR ≈ 3.517 kW,kW/TR = 用電 kW ÷ 冷量 TR。
  • PLR 是部分負荷比。先寫明分母採額定或當前可用冷量,再解讀曲線或型錄。

COP = cooling kW / electric kW. kW/TR = electric kW divided by cooling kW/3.517. Specify whether part-load ratio uses rated or currently available capacity.

常見錯誤 Common Mistakes

  • 在不同水溫或系統邊界直接比 COP。將條件並排。
  • 把機組功率當全站功率。記錄是否計入泵、塔及輔機。

Align water temperatures and include plant auxiliaries only where stated.

例題 Worked Example

呼出計算器 Open Calculator

冷水機供 35.17 kW 冷量,輸入 7 kW。COP 和 kW/TR?

  1. 冷量 35.17 kW ≈ 10 TR 35.17 kW cooling ≈ 10 TR
  2. 輸入 7 kW Input 7 kW
  3. 約 5.02 COP、0.70 kW/TR About 5.02 COP, 0.70 kW/TR
例題圖解 · 教學工況 Worked Diagram · Teaching Conditions
展開解題步驟 Show Solution

COP ≈ 5.02,35.17 ÷ 3.517 ≈ 10 TR,所以約 0.70 kW/TR。

完整示範與練習銜接 Worked Method and Practice Bridge

若比較另一筆相同冷量但冷卻進水更低的紀錄,先把同冷量的結果並列,再核對水溫與量測邊界,不能直接歸因於效率改善。 For a second record at the same load and lower condenser-entering water temperature, compare the results but verify water temperature and metering boundary before attributing the difference to an efficiency gain.

1 個小練習 Practice Problem

呼出計算器 Open Calculator

兩筆同冷量 70 kW 的虛構紀錄分別用電 13 和 16 kW,但冷卻水溫度不同。先算效率,再指出原始比較缺哪個對照條件。

作答後核對答案 Check Answer

13 kW 時 COP ≈ 5.38、0.653 kW/TR;16 kW 時 COP ≈ 4.38、0.804 kW/TR。要做公平對照,先補相同冷卻水進水溫度,並核對供水和負荷條件。

延伸思考與參考 Further Study and References

1 個蘇格拉底式問題 Socratic Question

如果某台機組的部分負荷指標較好,你還要什麼數據才能相信它適合這座示例冷凍站?

What site data would verify the benefit of a good part-load rating?

公開參考連結佔位符 Public Reference Placeholder