P2 專題選修 Specialist Elective · 9 分鐘 / min

一次側、二次側與解耦水路 Primary, Secondary and Decoupled Piping

從冷水機到末端盤管追蹤一次、二次與變流量一次水路。

開啟定量聯算教學 Open the Quantitative Engineering Lab

互動工程卡 Interactive Engineering Card

沿系統介面追蹤訊號、空氣或水路。 Trace signals, air or water through system interfaces.

  1. 冷凍水供水總管 Chilled-water supply header
  2. 負載盤管 Load coil
  3. 冷凍水回水總管 Chilled-water return header
一次二次冷凍水系統,接近零解耦流量時先依主供回水路追蹤熱量。 In this primary–secondary system, decoupler flow is near zero. Trace heat along the main distribution loop.

控制或設計判斷以題目工況為限,實案請核對適用要求。 This decision is scoped to the teaching condition. Verify the applicable requirements for real projects.

易錯做法 Common Mistake

未量測就固定解耦支路永遠單向。 Mark decoupler flow as permanently one-way without measuring it.

工程核對 Engineering Check

盤管在供回水之間。解耦流向視一次與二次流量差而定。 The coil links supply and return. Decoupler direction depends on the difference between primary and secondary flow.

延伸至相關知識卡 Continue to Related Cards · 泵揚程、流量與功率 Pump Head, Flow and Power · 冷凍水溫差偏低怎麼查 Troubleshooting Low Chilled-Water Delta T

追蹤一次、二次與解耦流向 Trace Primary, Secondary and Decoupler Flow

雙迴路水力示意 / Two-loop water circuit 泵 / Pump 冷水機 / Chiller 泵 / Pump 負載盤管 / Load coil 解耦管 / Decoupler

先讀泵的供水箭頭,再看負載回水。例題 8 − 6 = 2 L/s,餘量從供水流回回水管。把二次流量增加至 10 L/s,再預測流向。 Read the pump supply arrows, then trace the return. At 8 − 6 = 2 L/s, surplus goes from supply to return. Increase secondary flow to 10 L/s and predict the direction.

繪圖練習 Sketch Practice

在紙上畫出兩個環路,標上冷水機、兩台泵、負載及解耦管。先遮住算值,再畫出 8/10 L/s 時解耦管箭頭。 Sketch two loops. Label the chiller, both pumps, load and decoupler. Cover the readings, then draw the decoupler arrow for 8/10 L/s.

核對時從每台泵開始逐段跟回原點。8/10 L/s 時,解耦管由回水流向供水。 Check each circuit from its pump back to its start. At 8/10 L/s, the decoupler flows from return to supply.

中英術語 Key Terms
一次側
primary loop
二次側
secondary loop
解耦管
decoupler
旁通流量
bypass flow

查術語定義與用法 Look Up Definitions and Usage

學習目標 Learning Objective

在圖上標出冷水機、泵、旁通、盤管及解耦處,追蹤基本流向。

Label chillers, pumps, coils and bypass flow.

核心概念 Key Concepts

一次側送水通過主機。具二次迴路的圖上,負荷側另有泵,解耦管讓兩側流量可不相等。變流量一次側由同一循環服務主機及負荷,仍須核對各主機的使用範圍與最小流量。

The primary circuit feeds the chiller. A secondary pump serves loads, and a decoupler accommodates different flows. A variable-primary circuit serves both loads and chillers. Verify minimum and allowed machine flows.

公式與單位 Formulas and Units

  • 對有解耦管的簡圖,以 F解耦 = F一次 − F二次 定義正方向為由一次供水跨到回水,負值表示反向。三項統一用 L/s。
  • 套式前先標出流向和節點,平衡只適用於選定邊界。

Decoupler flow = primary minus secondary flow in L/s. Positive is supply to return. Negative is the reverse.

常見錯誤 Common Mistakes

  • 看到旁通管就假定固定方向。用兩側流量及箭頭核對。
  • 忽略單台設備最小流量。總流量可接受仍須看分配。

A bypass does not have a fixed direction. Check each machine's minimum flow.

例題 Worked Example

呼出計算器 Open Calculator

一次流量 10 L/s、二次 12 L/s。解耦管的流量與方向?

  1. 一次供水 10 L/s Primary supply 10 L/s
  2. 二次需要 12 L/s Secondary demand 12 L/s
  3. 回水經解耦管上行 2 L/s 2 L/s returns through decoupler to supply
例題圖解 · 教學工況 Worked Diagram · Teaching Conditions
展開解題步驟 Show Solution

10 − 12 = −2 L/s,也就是 2 L/s 由回水側流向供水側。

完整示範與練習銜接 Worked Method and Practice Bridge

用一次減二次得 −2 L/s,暖回水可能混入供水。若改為二次 9 L/s,方向翻轉,1 L/s 從供水去回水。 Primary minus secondary is −2 L/s, so warmer return water can mix into supply. With secondary flow at 9 L/s instead, 1 L/s flows from supply to return.

1 個小練習 Practice Problem

呼出計算器 Open Calculator

畫一個兩迴路的虛構水路。一次 11 L/s、二次分別為 8 和 13 L/s 的兩個情境,各標一次旁通流向,說明哪一個情境可能讓暖回水混入負荷供水。

作答後核對答案 Check Answer

二次 8 L/s 時是 +3 L/s,供到回;二次 13 L/s 時是 −2 L/s,回到供。在第二個情境,暖回水可能混入二次供水。

延伸思考與參考 Further Study and References

1 個蘇格拉底式問題 Socratic Question

如果主機供水溫度穩定但負荷側供水變暖,你會在圖上哪兩處加觀察點?

With stable plant supply and warmer load supply, where would you add measurements?

公開參考連結佔位符 Public Reference Placeholder

〔待導師填入:公開的冷凍站一次二次及變一次流量水路教學〕