中央空調穩態聯算 Steady-State Coupled HVAC Plant

教學模型:R134a、飽和吸氣與出冷凝器飽和液、無壓損、等焓節流。壓縮線為狀態連線,採用軸功邊界。 Teaching model: R134a, saturated suction and liquid leaving the condenser, negligible pressure drops, isenthalpic expansion. The compressor line joins end states. Power is stated at the shaft.

採用 CoolProp HEOS 的 R134a 物性表。蒸發 −10 至 15°C,冷凝 25 至 60°C。 R134a properties are tabulated from CoolProp HEOS. Evaporation −10 to 15°C; condensation 25 to 60°C.

房間及混風 → 乾盤管 → 冷凍水 → 製冷機 → 冷卻水 → 冷卻塔。定常熱平衡,定比熱,單一區域。塔與換熱逼近度由學生給定。不含潛熱、風泵電力、設備上限與控制暫態。 Zone and outdoor mix → dry coil → chilled water → refrigerator → condenser water → tower. Steady state, constant heat capacities, one zone. Enter exchanger and tower approaches. Latent load, fan and pump power, equipment limits and controls are outside this balance.

實線:循環端點。虛線:飽和液和飽和蒸氣邊界。壓力為絕對壓力。1 吸氣、2 排氣、3 冷凝出口、4 節流出口。 Solid: cycle endpoints. Dashed: saturated liquid and vapour boundaries. Pressure is absolute. 1 Suction, 2 discharge, 3 condenser outlet, 4 valve outlet.

q冷 = h₁ − h₄;w軸 = (h₂s − h₁) ÷ η;q排 = h₂ − h₃;h₄ = h₃。 qcool = h₁ − h₄; wshaft = (h₂s − h₁) ÷ η; qreject = h₂ − h₃; h₄ = h₃.

試驗:依次提高室外濕球與降低冷卻水量,預測哪個會提高冷凝壓力,並用塔排熱與壓縮軸功查證。 Experiment: raise outdoor wet bulb and then decrease condenser-water flow. Predict what happens to condensing pressure and verify it against tower heat rejection and shaft work.

各水路 Q = ṁ cₚ ΔT。聯立冷凝器排熱、塔出水與冷凝逼近度求冷凝溫度。 Each water loop uses Q = ṁ cₚ ΔT. Solve condenser rejection, tower outlet and condenser approach together to find condensation temperature.