P1 應用延伸 Applied Extension · 8 分鐘 / min

建築壓差、風壓與煙囪效應 Building Pressure, Wind and Stack Effect

用供排風收支理解濕氣或氣味的遷移方向。

互動工程卡 Interactive Engineering Card

用現有證據選擇下一步查驗。 Use the available evidence to select the next check.

即使送風大於排風,開側門後壓差表的極性會變。 Despite supply exceeding exhaust, opening a side door reverses the differential-pressure reading.

控制或設計判斷以題目工況為限,實案請核對適用要求。 This decision is scoped to the teaching condition. Verify the applicable requirements for real projects.

易錯做法 Common Mistake

用送排風量差直接標出所有房間的 Pa。 Convert supply minus exhaust directly into a pressure value in every room.

工程核對 Engineering Check

壓差還受洩漏、開口和風力影響,風量差無法單獨定量。 Pressure also depends on leakage, openings and wind. Flow imbalance alone cannot quantify it.

延伸至相關知識卡 Continue to Related Cards · 分區、送風與回風路徑 Zoning and Supply/Return Air Paths · 廚房補風、轉移風與鄰區壓差 Kitchen Makeup Air, Transfer Air and Room Pressure

中英術語 Key Terms
建築壓差
building pressure difference
風壓
wind pressure
煙囪效應
stack effect
外洩
exfiltration

查術語定義與用法 Look Up Definitions and Usage

學習目標 Learning Objective

辨認正負壓、供排風平衡,以及風和室內外溫差帶來的干擾。

Identify relative pressure, wind and stack effects.

核心概念 Key Concepts

空氣會沿開口由較高壓流向較低壓。正負壓都要說明相對哪個空間。風向會改變不同外牆的壓力,室內外空氣密度差也可能使不同高度的壓差方向不同。門開啟時,局部壓差與流路可能突然改變。混風系統增加新風時,也要確認多出的空氣能否經排氣口或洩壓風機離開。

Air flows through an opening from higher to lower pressure. State the reference when describing positive pressure. Wind changes facade pressure. Density differences can reverse the pressure sign with height. Opening a door changes local resistance. Additional outdoor air needs a relief path.

公式與單位 Formulas and Units

  • Δp = p房間 − p鄰區,單位 Pa。
  • 同密度近似下,以「送入風量 − 有組織排出風量」找需要由滲透、外洩等途徑補平的風量。Pa 無法直接由 L/s 相減得到。

Δp = proom − padjacent in Pa. At nearly equal density, supplied minus organized exhaust volume must leave through other paths. L/s is not Pa.

常見錯誤 Common Mistakes

  • 把風量收支當成測得的 Pa。需要壓差計或流阻模型。
  • 漏寫參考空間或門況。在壓差旁記錄兩側位置、高度及門的狀態。

Pressure requires a measurement or resistance model. Record the reference space, height and door state.

例題 Worked Example

呼出計算器 Open Calculator

房壓 3 Pa、鄰區 8 Pa,兩者同表壓基準。壓差和可能氣流方向?

  1. 鄰區 8 Pa Adjacent 8 Pa
  2. 門口:可能向房間 Door: likely into room
  3. 房間 3 Pa Room 3 Pa
例題圖解 · 教學工況 Worked Diagram · Teaching Conditions
展開解題步驟 Show Solution

Δp = 3 − 8 = −5 Pa。有連通開口時,氣流傾向由鄰區進入房間。

完整示範與練習銜接 Worked Method and Practice Bridge

房間減鄰區為 −5 Pa。若另有 190 送、175 L/s 排,房間淨流量需向外 15 L/s,不代表每個開口都向外。開門改變阻力與壓差,需重新量測。 Room minus adjacent is −5 Pa. If separate totals are 190 supply and 175 L/s exhaust, 15 L/s net must leave, though individual paths can differ. An open door changes resistance and pressure, so remeasure.

1 個小練習 Practice Problem

呼出計算器 Open Calculator

虛構房間送入 240 L/s,有組織排走 210 L/s。畫出剩餘風的可能出路,解釋一扇鄰區門開啟為何可能改變觀測結果。

作答後核對答案 Check Answer

240 − 210 = 30 L/s 尚需由其他路徑排出,可在圖上畫向鄰室或室外的開口。門開啟會改變阻力與流路,壓差與分配可能改變。

延伸思考與參考 Further Study and References

1 個蘇格拉底式問題 Socratic Question

如果一樓門口和樓上外牆的壓差方向不同,你會如何設計兩筆量測以區分風與煙囪效應?

How would two measurements help separate wind and stack effects at different heights?

公開參考連結佔位符 Public Reference Placeholder

〔待導師填入:公開的建築壓差、滲風、風效應及煙囪效應資料〕