P2 專題選修 Specialist Elective · 9 分鐘 / min

VAV 箱、風閥與再熱 VAV Terminals, Dampers and Reheat

比較壓力相關、壓力獨立、雙風道和風機輔助末端。

互動工程卡 Interactive Engineering Card

在工況下定位部件與用途。 Identify a component and its purpose in this condition.

流量感測 / Flow sensor 風閥 / Damper 再熱盤管 / Reheat coil
圖例顯示有風量感測器、風閥和一個再熱盤管。 A terminal schematic shows an airflow sensor, damper and reheat coil.

控制或設計判斷以題目工況為限,實案請核對適用要求。 This decision is scoped to the teaching condition. Verify the applicable requirements for real projects.

易錯做法 Common Mistake

把再熱盤管標作新風測量點。 Label the reheat coil as the outdoor airflow measuring point.

工程核對 Engineering Check

沿風路辨認量測、調量與換熱三個功能。 Locate the measuring, volume-control and heat-transfer functions along the airflow path.

延伸至相關知識卡 Continue to Related Cards · VAV 系統如何按區送風 Variable Air Volume by Zone · 感測器、致動器與點位表 Sensors, Actuators and Point Lists

中英術語 Key Terms
變風量末端
VAV terminal
風閥
damper
再熱
reheat
回授
feedback
靜壓
static pressure

查術語定義與用法 Look Up Definitions and Usage

學習目標 Learning Objective

辨認幾種常見末端形式,並解釋風壓變動時控制器需要什麼訊號。

Recognize terminal types and what they sense when static pressure changes.

核心概念 Key Concepts

壓力相關風閥主要按開度工作,主管壓力改變時同一開度可能得到不同風量。壓力獨立末端另用量測風量作回授,在可控制範圍內修正風閥。單風道可帶再熱盤管,雙風道在混合點調兩股風,風機輔助型另有風機與回引路徑。

A pressure-dependent damper at the same position may deliver a different flow when duct pressure changes. A pressure-independent terminal measures flow and adjusts the damper within its working range. Single ducts may include reheat, dual ducts mix streams, and fan-powered terminals add another airflow path.

公式與單位 Formulas and Units

  • 風量偏差 = 設定風量 − 回授風量,單位 L/s。
  • 記錄風閥開度(%)、風量(L/s)與可用靜壓(Pa),三者各有含義。

Flow error = setpoint minus feedback in L/s. Record position %, flow L/s and available static pressure Pa separately.

常見錯誤 Common Mistakes

  • 把開度百分比當成風量百分比。用風量回授才可確認。
  • 以為壓力獨立等於無壓力下限。留意量測範圍及風閥是否已飽和。

Damper position is not proportional to airflow by definition. A pressure-independent terminal still needs minimum pressure.

例題 Worked Example

呼出計算器 Open Calculator

設定 140 L/s,回授 126 L/s。風量偏差以設定減實測為多少?

  1. 目標 140 L/s Target 140 L/s
  2. 回授 126 L/s Feedback 126 L/s
  3. 偏差 +14 L/s Error +14 L/s
例題圖解 · 教學工況 Worked Diagram · Teaching Conditions
展開解題步驟 Show Solution

140 − 126 = +14 L/s。控制器還需依可用靜壓等條件決定是否加大風閥開度。

完整示範與練習銜接 Worked Method and Practice Bridge

畫「目標 → 控制器 → 風閥 → 風管」及「流量測點 → 控制器」。若量測可信且閥仍有行程,控制器可增加開度;固定開度不保證固定流量。 Draw target → controller → damper → duct and airflow sensor → controller. The controller can open the damper if feedback is valid and travel remains. Fixed position does not ensure fixed airflow.

1 個小練習 Practice Problem

呼出計算器 Open Calculator

虛構末端的風量目標是 120 L/s。主管壓力改變後,風閥維持原位,讀值降至 96 L/s。算偏差,畫出加上風量回授後需要的訊號路徑。

作答後核對答案 Check Answer

120 − 96 = +24 L/s。訊號可畫「風量設定值 → 控制器 → 風閥 → 風管風量 → 感測器 → 控制器」。

延伸思考與參考 Further Study and References

1 個蘇格拉底式問題 Socratic Question

若風閥已全開且風量仍不足,你會用什麼證據判斷問題在控制器或系統可用壓力?

If the damper is at 100% and airflow is low, what evidence distinguishes control from pressure limits?

公開參考連結佔位符 Public Reference Placeholder

〔待導師填入:公開的 VAV 末端形式及風量回授資料〕