P1 應用延伸 Applied Extension · 9 分鐘 / min

比對模型、量測與敏感度 Model Validation and Sensitivity

用變量、測量偏差和獨立資料分辨假設及錯誤。

互動工程卡 Interactive Engineering Card

用現有證據選擇下一步查驗。 Use the available evidence to select the next check.

模型和實測都顯示 kW,但模型取整點,儀表取 15 分鐘平均。 Model and meter both show kW, but the model samples an instant and the meter gives a 15-minute average.

控制或設計判斷以題目工況為限,實案請核對適用要求。 This decision is scoped to the teaching condition. Verify the applicable requirements for real projects.

易錯做法 Common Mistake

直接用兩個數字的差調整所有模型係數。 Tune every model coefficient from the raw difference.

工程核對 Engineering Check

量測與模型時段一致後,差異才適合作為校準證據。 Only after aligning measurement and model timing is the difference suitable for calibration.

延伸至相關知識卡 Continue to Related Cards · 節能前後怎樣公平比較 Fair Before-and-After Energy Verification · 計算附錄與獨立驗算 Calculation Appendix and Independent Checks

中英術語 Key Terms
模型驗證
model validation
靈敏度
sensitivity
模擬值
simulated value
殘差
residual

查術語定義與用法 Look Up Definitions and Usage

學習目標 Learning Objective

用一組試算及量測判斷偏差,並設計只改一個輸入的敏感度檢查。

Calculate residuals and design a one-variable sensitivity test.

核心概念 Key Concepts

模型常因負荷、氣象、時段、測量和設備曲線而偏離讀值。先對齊系統邊界及時鐘,再看偏差是在某類工況集中。校正用過的資料適合調整模型,另用保留資料檢查模型能否解釋新情境。

Loads, weather, equipment curves and measurement timing can cause differences. Align boundary and time. Use held-out measurements to validate the calibrated model.

公式與單位 Formulas and Units

  • 殘差 = 模擬值 − 量測值,依變數用 kW、kWh 或 K。
  • 百分比殘差用非零的量測值作分母。量測接近零時用原單位描述差異較清楚。

Residual = simulated − measured in matching units. Divide by nonzero measured value for a relative residual. Near zero use the original unit.

常見錯誤 Common Mistakes

  • 把不同時段的總量直接比較。先對齊取樣時間。
  • 一次調很多輸入再給出唯一原因。每輪只改一個,或明確記錄實驗設計。

Do not compare mismatched sample windows. Vary one parameter at a time or document the test design.

例題 Worked Example

呼出計算器 Open Calculator

模型 18 kW,量測 20 kW。算殘差及相對殘差。

  1. 模型 18 kW Model 18 kW
  2. 量測 20 kW Measured 20 kW
  3. 模型減量測 −2 kW、−10% Model minus measured −2 kW, −10%
例題圖解 · 教學工況 Worked Diagram · Teaching Conditions
展開解題步驟 Show Solution

按模擬減量測為 −2 kW,除以量測值得 −10%。

完整示範與練習銜接 Worked Method and Practice Bridge

逐時對齊後才相減,百分比以量測為基準。若另一時點為 22 對 20 kW,殘差翻正,應查工況相關輸入,不能以平均抵銷誤差。 Align intervals and divide residual by measured value. A later 22 versus 20 kW changes the sign, so inspect operating inputs rather than canceling residuals by averaging.

1 個小練習 Practice Problem

呼出計算器 Open Calculator

一個虛構下午的三段模擬功率是 12、14、18 kW,量測是 13、15、16 kW。逐段列殘差,選一個輸入做下一輪敏感度檢查。

作答後核對答案 Check Answer

逐段為 −1、−1、+2 kW。可固定其他輸入,只改占用率或冷卻水溫,觀察三段偏差是否縮小,並記錄模型版本。

延伸思考與參考 Further Study and References

1 個蘇格拉底式問題 Socratic Question

若總用電一致、逐段殘差卻一正一負互相抵消,你會增加哪種驗證?

How would you detect canceling errors when energy totals agree?

公開參考連結佔位符 Public Reference Placeholder

〔待導師填入:公開的建築能耗模型驗證與測量對比資料〕